Fire Extinguisher Simulator
Choose the right extinguisher, then pull, aim, squeeze and sweep on a live fire — in 3D, in your browser
Display controls
Which extinguisher on which fire?
1 Overview
The Fire Extinguisher Simulator is a workshop with a fire point of 12 extinguishers on the wall (11 types and a fire blanket) and 10 fires to deal with: wood and paper by the workbench, a solvent tray, a leaking gas cylinder, magnesium swarf in a lathe, a distribution board, a deep-fat fryer, an e-bike battery, a power-tool battery on charge, and two fires that are already too big to fight. Each extinguisher acts on each fire the way its agent really does: the right one puts the fire out, a weak one leaves embers that re-ignite, and a dangerous one makes it worse.
2 Train: do the drill yourself
Pick a fire. A coach in the panel takes you through the drill one step at a time, saying what to do and why, and what to press glows in the room. Raise the alarm turns to the call point by the exit: in the US you lift the clear cover of the pull station and pull the handle down; in the UK and Europe you press the call point's element in and its flag shows. The sounder above it then flashes and rings. Size up the fire shows you the fire with its size, then your way out drawn on the floor, then whether its supply can be shut off. To choose, the coach names the fire's class and the extinguishers that suit it, and Open the selection chart shows every extinguisher against every fire with this one's column marked; press a square to see why. Read the label, check the gauge, pull the pin and test-squirt, then Go to the fire and Walk into reach: the green band on the floor is where to stand with that extinguisher. The ring on the floor shows where the stream will land: green on the base of the fire, amber on the flames or its edge, grey when you are too far. Hold Squeeze (or Space) and drag left and right to sweep the whole base. Once it is out, watch it for 10 seconds, then back away facing it. Drag to aim (or A and D to turn and R and F to raise and lower the nozzle), and W and S step in and back. The debrief scores each step and Print practice summary gives you a record of the run.
3 Show me how
A trainer does the whole drill for the fire you picked, with a caption for each step and the camera following the action. Play, pause, step back and forward (or Space and the arrow keys) and drag the scrubber to any moment. Tick Show me the mistake to watch one of the 10 mistake clips: the common wrong choice for that fire, such as water on a burning fryer, and what it does.
4 How it works
How it works cuts an extinguisher in half so you can see inside: the agent, the nitrogen above it, the dip tube, the valve with its seal, spring and stem, the lever, the pin, the gauge and the hose. Pull the pin (click it, or the button), then hold the lever (press and hold it in 3D, hold the button, or hold Space) and watch the gas push the agent up the dip tube and out of the nozzle. Let go and the valve snaps shut. Hold it until it is empty and the plot shows the pressure falling as the gas expands. The readings give the pressure, the agent left, the flow and the force on your hand. Choose any extinguisher; the powders can also be shown cartridge-operated, and CO₂ is shown as the liquid under its own vapour pressure. The page opens here.
5 Quiz: Practical, Theory or Mixed
The Quiz starts with a choice. Practical is 5 questions in the workshop with no hints: 3 ask for the right first action for a fire (click it in the room or pick it from the list, and the reason follows), and 2 are whole drills you do on your own, from the alarm to backing away, passed or failed on the same scoring as Train. Theory asks 10 questions from a 25-question pool, written for the region you choose. Mixed is 5: 1 drill, 2 first-action questions and 2 theory questions.
6 Regions, units and sound
US · NFPA 10 and UK & Europe · BS EN 3 change the labels, class letters, colour bands and rules to the ones you will meet at work; the fire behaves the same. SI and Imperial change the units. Sound is synthesised in the browser and starts only when you press a button; on a phone it is off until you turn it on.
Fire Extinguisher Simulator — Virtual Fire Extinguisher Training in Your Browser
Most people meet a fire extinguisher for the first time in an emergency. This free fire extinguisher simulator lets you practise first: choose the right extinguisher for the fire in front of you, check it, pull the pin and use the PASS technique on a fire that reacts the way it really would — going out, coming back, or flaring up when the wrong agent hits it. It runs in 3D in a browser on a computer, tablet or phone, with no app or VR headset, and its How it works mode cuts an extinguisher in half so you can watch what the pin, the lever and the valve do.
The fire is a teaching model: it is set so that each extinguisher deals with a fire of the size its rating describes, and each agent works on each fuel as the makers' datasheets and fire-safety guidance say. It shows the right choices and the wrong ones clearly; it is not a prediction of a real fire test.
Types of Fire Extinguishers and Their Uses
Every extinguisher is made for certain kinds of fire, and some are dangerous on others. The table lists the extinguishers in the simulator, the classes each is rated for in the UK and Europe and in the US, the fires on which it makes things worse, and a typical size and rating.
| Extinguisher | Use on (UK & Europe) | Use on (US) | Never use on | Size · rating (UK & Europe) | Size · rating (US) |
|---|---|---|---|---|---|
| Water jet / Water (stored pressure) | Class A | Class A | Flammable liquid, Combustible metal, Live electrical equipment, Cooking oil | 9 L · 21A | 2.5 gal · 2-A |
| Water spray with additive | Class A | Class A | Flammable liquid, Combustible metal, Live electrical equipment, Cooking oil | 6 L · 27A | 6 L · 27A |
| Water mist | Class A, Electrical, Class F | Class A, Class C, Class K | Combustible metal | 6 L · 13A 40F | 2.5 gal · 2-A:C |
| AFFF foam / AR-AFFF foam | Class A, Class B | Class A, Class B | Combustible metal, Live electrical equipment, Cooking oil | 6 L · 21A 144B | 2.5 gal · 3-A:20-B |
| CO₂ / Carbon dioxide (CO₂) | Class B, Electrical | Class B, Class C | Combustible metal, Cooking oil | 2 kg · 34B | 5 lb · 5-B:C |
| ABC dry powder / ABC dry chemical | Class A, Class B, Class C, Electrical | Class A, Class B, Class C | — | 6 kg · 43A 233B C | 5 lb · 2-A:10-B:C |
| BC powder / BC dry chemical | Class B, Class C, Electrical | Class B, Class C | — | 5.5 lb · 40-B:C | 5.5 lb · 40-B:C |
| Metal-fire powder (Class D) / Class D (sodium chloride) | Class D | Class D | — | 9 kg · D | 30 lb · D |
| Wet chemical / Class K wet chemical | Class A, Class F | Class A, Class K | Combustible metal, Live electrical equipment | 6 L · 13A 75F | 6 L · 2-A:K |
| Clean agent (FK-5-1-12) / Clean agent (Halotron I) | Class B, Electrical | Class B, Class C | Combustible metal | 6 kg · 34B | 5 lb · 5-B:C |
| Lithium-ion (AVD) | Class A, Lithium-ion | Class A, Lithium-ion | Combustible metal, Live electrical equipment, Cooking oil | 6 L · 13A | 6 L · A (UL listed) |
| Fire blanket | Class F | Class K | — | 1.2 × 1.2 m · BS EN 1869 | 1.2 × 1.2 m · BS EN 1869 |
Fire Extinguisher Colour Codes
In the UK and Europe (BS EN 3) every extinguisher body is red, with a coloured band naming the agent. In the US nearly every extinguisher is red all over, so the only way to tell them apart is the label: its name, UL rating and pictographs.
| Extinguisher | UK & Europe (BS EN 3): red body with a | US: red body, read the label |
|---|---|---|
| Water jet | Red band | Water (stored pressure) · 2-A |
| Water spray with additive | Red band | Water spray with additive · 27A |
| Water mist | White band | Water mist · 2-A:C |
| AFFF foam | Cream band | AR-AFFF foam · 3-A:20-B |
| CO₂ | Black band | Carbon dioxide (CO₂) · 5-B:C |
| ABC dry powder | Blue band | ABC dry chemical · 2-A:10-B:C |
| BC powder | Blue band | BC dry chemical · 40-B:C |
| Metal-fire powder (Class D) | Blue band | Class D (sodium chloride) · D |
| Wet chemical | Yellow band | Class K wet chemical · 2-A:K |
| Clean agent (FK-5-1-12) | Green band | Clean agent (Halotron I) · 5-B:C |
| Lithium-ion (AVD) | White band | Lithium-ion (AVD) · A (UL listed) |
| Fire blanket | Red wall case | Fire blanket · BS EN 1869 |
Classes of Fire
Fires are grouped by what is burning. The letters differ between the two systems: a cooking-oil fire is Class F in Europe and Class K in the US, and a gas fire is Class C in Europe but Class B in the US. Europe gives electrical fires no letter at all.
| What is burning | UK & Europe | US | Right extinguishers | Dangerous on it |
|---|---|---|---|---|
| Wood, paper and cardboard | Class A | Class A | Water jet, Water spray with additive, Water mist, AFFF foam, ABC dry powder, Wet chemical, Lithium-ion (AVD) | — |
| Flammable liquid (petrol, solvent) | Class B | Class B | AFFF foam, CO₂, ABC dry powder, BC powder, Clean agent (FK-5-1-12) | Water jet, Water spray with additive |
| Flammable gas (propane) | Class C | Class B | ABC dry powder, BC powder | — |
| Combustible metal (magnesium swarf) | Class D | Class D | Metal-fire powder (Class D) | Water jet, Water spray with additive, Water mist, AFFF foam, CO₂, Wet chemical, Clean agent (FK-5-1-12), Lithium-ion (AVD) |
| Live electrical equipment | Electrical | Class C | Water mist, CO₂, ABC dry powder, BC powder, Clean agent (FK-5-1-12) | Water jet, Water spray with additive, AFFF foam, Wet chemical, Lithium-ion (AVD) |
| Cooking oil (deep-fat fryer) | Class F | Class K | Water mist, Wet chemical, Fire blanket | Water jet, Water spray with additive, AFFF foam, CO₂, Lithium-ion (AVD) |
| Lithium-ion battery | Lithium-ion | Lithium-ion | Lithium-ion (AVD) | — |
The PASS Technique
Pull the pin, Aim low at the base of the fire, Squeeze the lever, Sweep from side to side. Before that, raise the alarm, make sure your exit is behind you, and test-squirt briefly away from the fire. Afterwards, back away facing the fire: it can flare up again. An extinguisher empties in seconds, so short, aimed bursts at the base go further than a long spray at the flames.
How a Fire Extinguisher Works
A fire needs heat, fuel, oxygen and a chemical chain reaction — the fire tetrahedron. Water cools; foam and CO₂ smother; dry powder breaks the chain reaction; wet chemical cools burning oil and forms a soapy crust over it. In a stored-pressure extinguisher the agent shares the shell with nitrogen, which drives it up the dip tube as soon as the valve opens, and the gauge shows that pressure. A cartridge-operated extinguisher is unpressurised until a striker punctures a gas cartridge inside it. A CO₂ extinguisher holds liquid CO₂ under its own pressure and has no gauge; it is checked by weighing.
Electrical, Kitchen, Lithium-Ion and Gas Fires
Electrical: water and foam conduct, so on live equipment they can shock you. Isolate the power if it is safe to, and use CO₂ or powder. Kitchen: never put water on burning oil — it flashes to steam and throws the oil out as a fireball. Turn the heat off and use a wet chemical extinguisher or a fire blanket. Lithium-ion: for an e-bike or e-scooter battery, get out and call the fire service; small packs can be cooled with an AVD extinguisher. Gas: shut the supply off and let the flame burn out; putting it out with gas still flowing leaves an explosive cloud.
Inspection and Servicing
In the US, OSHA requires a visual check every month and a maintenance check every year, plus a hydrostatic test every 5 or 12 years depending on the type. In the UK, BS 5306-3 calls for a service by a competent person at least once a year. Between services, anyone can check that the extinguisher is in place, the pin and seal are intact and the gauge needle is in the green.
Who Uses This Simulator?
Employers and safety officers running annual fire awareness, fire wardens and marshals, apprentices and students on workshop and vocational safety courses, teachers, and anyone who wants to know which extinguisher to grab before they need one. It is not a substitute for hands-on training: in the US, OSHA 29 CFR 1910.157(g) requires employers to train employees who are expected to use extinguishers, on hire and every year, and local law sets similar duties elsewhere.
Frequently Asked Questions
What are the main types of fire extinguisher?
The common types are water, foam, dry powder, CO2 and wet chemical, plus specialist ones: water mist, Class D powder for metals, clean agent and AVD for lithium-ion batteries. Each is rated for certain classes of fire, and using the wrong one can make a fire worse.
Which fire extinguisher is used on an electrical fire?
Use CO2 or dry powder, which do not conduct electricity, and isolate the power first if it is safe to. Never use water or foam on live equipment. A water mist extinguisher may only be used if it has passed the 35 kV dielectric test, at least 1 m away, on equipment up to 1000 V.
What does PASS stand for in fire extinguisher use?
Pull the pin, Aim at the base of the fire, Squeeze the lever, Sweep from side to side. Before you start, raise the alarm and keep your exit behind you; afterwards, back away facing the fire.
Can you put water on a burning deep-fat fryer?
No. Water turns to steam under the hot oil and throws it out as a fireball. Switch the heat off if you can, then use a wet chemical extinguisher (Class F in Europe, Class K in the US) or lay a fire blanket over the pan and leave it there. The oil re-ignites by itself above about 392 degrees C.
How do you put out a lithium-ion battery fire?
For an e-bike, e-scooter or other large battery, get out, close the door and call the fire service: the cells keep venting and re-igniting. A small pack, such as a power-tool battery, can be cooled with an AVD extinguisher; the 6 L unit is rated for packs of 250 to 500 Wh.
How often must fire extinguishers be inspected?
In the US, OSHA requires a visual inspection every month and a maintenance check every year, with hydrostatic tests every 5 or 12 years depending on the type. In the UK, BS 5306-3 calls for a service by a competent person at least once a year.
Can a fire extinguisher simulator replace real training?
No. A simulator is practice for choosing the right extinguisher and learning the drill. It does not replace hands-on training with a real extinguisher, which OSHA 29 CFR 1910.157(g) requires on hire and at least once a year.
Explore Related Simulators
- House Wiring Simulator: how circuits are protected, and why isolating the power matters.
- Ideal Gas Law Simulator: the pressure inside a stored-pressure extinguisher and a CO₂ cylinder.
- Pressure Vessel Simulator: the stresses in a pressurised shell, and why extinguishers are pressure-tested.
- Heat Treatment Simulator: hot metal in a workshop, from furnaces to quench tanks.
- Welding Symbols: another workshop skill where reading the label right comes first.
Sources
Every figure in the simulator comes from a published source: makers' datasheets, standards and fire-safety guidance. They are listed here by their short codes.
- [AMX18] Amerex, *Portables Product Catalog 2018* — cdn1.shipserv.com/ShipServ/pages/profiles/71412/documents/Po
- [FC-W] Firechief XTR Water FXW6/FXW9 product sheet — www.fireprotectionshop.co.uk/storage/fxw6_fxw9_product_sheet
- [FC-WA] Firechief XTR EcoSpray Water Additive — m2.prod.safetybuyer.com.cfstack.com/media/wysiwyg/Firechief_
- [FC-WM] Firechief PureSafe Water Mist — static.thesafetysupplycompany.co.uk/0PezpNORpuyQSm8cSBbgSaHi
- [FC-F] Firechief XTR AFFF Foam — cdn.aws.toolstation.com/items/coshh/62327.pdf
- [FC-C] Firechief XTR CO2 — m2.prod.safetybuyer.com.cfstack.com/media/wysiwyg/FIRECHIEF_
- [FC-P] Firechief XTR ABC Powder — www.smigroupuk.com/storage/uploads/products/document/fmp1-fx
- [PROTEC-D] Protec, Lithium L2 and M28 powder extinguishers (9325/00 data) — www.protec.co.uk/our-products/portable-fire-extinguishers/li
- [CMD-WC] Commander 6 L Wet Chemical FX-WCH-006-DCF datasheet — startsafety.uk/cdn/shop/files/commander-6ltr-wet-chemical-fi
- [CF-FK] Ceasefire Clean Agent FK-5-1-12 6 kg datasheet — www.farnell.com/datasheets/4252860.pdf
- [FC-LX] Firechief Lith-Ex FLE product sheet — www.fireprotectionshop.co.uk/storage/fle1_fle2_fle6_fle9_pro
- [RS-FB] RS PRO soft-case fire blankets (BS EN 1869:2019) — docs.rs-online.com/1ff1/A700000013166920.pdf
- [GLA] University of Glasgow / Safelincs extinguisher guide — www.gla.ac.uk/media/Media_185169_smxx.pdf
- [FSC-COL] Fire and Safety Centre, guide to extinguisher colours — www.fireandsafetycentre.co.uk/blogs/news/a-comprehensive-gui
- [FSC-SITE] Fire and Safety Centre, siting of extinguishers (BS 5306-8) — www.fireandsafetycentre.co.uk/advice-centre/siting-of-exting
- [FSC-SM] Fire and Safety Centre, service and maintenance (BS 5306-3: annual service) — www.fireandsafetycentre.co.uk/pages/service-and-maintenance
- [WCC] Warwickshire County Council, fire extinguishers (UK classes) — www.warwickshire.gov.uk/fireextinguishers
- [FIA97] FIA Fact File 97, EN 3-7 dielectric test — fia.uk.com/news/fact-file-97-en-3-7-dielectric-test.html
- [OSHA157] OSHA 29 CFR 1910.157 — www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.
- [OSHA-ET] OSHA Evacuation eTool, portable extinguishers (archived) — webarchive.library.unt.edu/eot2008/20080918015207/http://osh
- [OSHA-FF] OSHA Evacuation eTool, fight or flee (archived) — webarchive.library.unt.edu/eot2008/20090508021608/http://www
- [SFE-SYM] Serviced Fire Equipment, extinguisher symbols — servicedfireequipment.com/what-do-the-symbols-on-a-fire-exti
- [SFE-NFPA10] Serviced Fire Equipment, NFPA 10 placement guide — servicedfireequipment.com/nfpa-10-placement-spacing-guide/
- [NFPA10-MT] NFPA 10 §6.1.3.8 mounting heights as quoted at and — dustinphillipsconsulting.substack.com/p/how-high-is-too-high
- [STEW21] Stewart et al., J. Loss Prev. Process Ind. 71 (2021) 104495, Tables 1–2 (gasoline pool, SFPE 2002) — eprints.whiterose.ac.uk/173731/1/1-s2.0-S0950423021001042-ma
- [NIST2133] Hu et al., NIST TN 2133, The Character of Residential Cooktop Fires — doi.org/10.6028/NIST.TN.2133
- [NIST-PAL] NIST Fire Calorimetry Database, 4 pallets — www.nist.gov/node/1674266
- [NIST-BSK] NIST Fire Calorimetry Database, waste basket — www.nist.gov/node/1674076
- [NIST-PROP] NIST Fire Calorimetry Database, propane burner check — www.nist.gov/node/1839901
- [CAMEO-MG] NOAA CAMEO Chemicals, magnesium — cameochemicals.noaa.gov/chemical/6949
- [FSRI-ES] FSRI/UL e-scooter battery tests (Firehouse) — firehouse.com/home/article/53063930/at-the-core-what-firefig
- [NFCC-EB] NFCC e-bike and e-scooter guidance — nfcc.org.uk/wp-content/uploads/2023/09/NFCC_Guidance_E-bikes
- [USFA-LI] US Fire Administration, lithium-ion batteries — www.usfa.fema.gov/a-z/lithium-ion-batteries/risks-and-respon
- [IGEM-GAS] IGEM, Safety advice for emergency services attending gas escapes (2009 v2) — www.igem.org.uk/asset/2D00ECF8-68F6-43E3-B3EF84F5B6E1FDAB
- [NOTTS-CP] Nottinghamshire FRS, chip pan fire warning — www.notts-fire.gov.uk/news/warnings-issued-following-chip-pa
- [HESK83] Heskestad, Luminous heights of turbulent diffusion flames, Fire Saf. J. 5 (1983) 103–108, as printed in arXiv 2008.12209 eq. 18 — arxiv.org/pdf/2008.12209
- [CBC907] 2022 California Building Code §907 manual fire alarm box height — www.corada.com/documents/2022CBCPG/chapter-9-fire-protection
- [BS5839] BS 5839-1 manual call point 1.4 m ± 200 mm (secondary summaries; standard not seen)
- [AVD6L] National Fire Supply, AVD6L (UL Class A listing) — nationalfiresupply.com/product/avd6l-6-liter-avd-fire-exting
- [NIST-CO2] NIST Chemistry WebBook, carbon dioxide saturation properties — webbook.nist.gov/cgi/fluid.cgi?ID=C124389&Action=Load&Type=S
3D Model Credits
The workshop's furniture and machines are openly licensed 3D models, simplified and refitted for this simulator. Under CC BY 4.0: Old Work Bench by Oliver Triplett; Lathe Machine by ridhobahri; Electrical Distribution Cabinet by fdgasd7; Kitchen Counter by FordVFX; city E-bike by rummsfeld (licence: CC BY 4.0). Shelves, drill, hand truck, power box, steel shelving, tool chest, tool cart and toolbox are CC0 models from Poly Haven.